AC Power Cable, 5,000 Volt, 60 Hertz, Procurement Of, Specification For

Document ID 
KSC-SPEC-E-0022
Document Date 
07/24/1996

This specification provides data for the procurement of single-conductor 5,000-volt, 60-hertz, alternating current (ac) power cable with ethylene propylene rubber (EPR) insulation, concentric neutral and overall jacket for replacement of existing circuits only. New 5-kilovolt (kV) circuits should use 15,000-volt cable per KSC-SPEC-E-0023.
Cables included in this specification shall be suitable for single phase or three phase circuit in aerial or underground in ducts or direct burial. The cable shall be rated for 90 degree Celsius (°C) continuous conductor temperature, 130 °C emergency overload, and 133-percent insulation level.